When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the cause of this leakage.
Ice dams are ridges of ice that occur along eaves with overhangs (Photo 1). This water and ice build-up can cause leakage and damage to the underlying interior space and possibly result in safety concerns such as structural collapse, mold growth, and falling ice. Ice dams result in millions of dollars in damage and insurance claims each year.
Ice Dam Formation
Accumulated snow on roofs acts as an insulation layer. If the underlying roof
surface exceeds the freezing temperature of water (i.e. roofs over heated spaces),
the underside of the snow layer will melt. Sources that melt the snow include
heat from the underlying conditioned space, ambient heat, and solar radiation.
The melt water will run down the roof toward the eaves. When it reaches cold,
un-insulated overhangs, it freezes and forms a layer of ice. As this process
continues, the ice height increases, creating a dam that retains melt water.
This ponded water backs up and flows past the dry laps in the underlayment,
resulting in interior leakage and subsequent damage (Figure 1). The damage is
most severe in areas with frequent freeze-thaw cycles. Water that overflows
the dam also creates icicles along the eave (Photo 2).
Methods of Prevention
There are several methods of preventing ice dams and subsequent damage including:
• Insulating the ceiling line to keep attic space cold.
• Ventilating the attic space or roof framing cavity to keep the attic
cold.
• Specifying appropriate materials at possible ice dam locations to prevent
leakage through roof underlayment laps.
• Heating portions of the roof that could be susceptible to ice dam formation.
• Performing preventive maintenance prior to and during the winter.
Insulated ceilings and ventilated attics that create a cold roof surface are the best methods to prevent ice dams. All methods are discussed below.
Insulation
Insulation should be placed in the attic to retard the conductive heat flow
from the conditioned space to the exterior. Areas that leak heat, such as exhaust
fans, ducts, chimneys, attic hatches, and pipe penetrations through the ceiling
need to be sealed. Since living space contains warm moist air and the attic
space above insulation contains dry colder air during the winter, a vapor barrier
is placed on the warm side of the insulation to stop moisture transfer to the
attic. The vapor barrier, typically a 4 mil to 6 mil thick polyethylene sheet,
is placed between the interior finish and insulation/framing.
Ventilation
Ventilating the attic space or roof framing cavity will help keep the roof surface
cold during the winter and remove moisture from the attic space. The two forces
that provide ventilation for attics and framing cavities are convection and
wind. Cold air enters at low vents (at eaves) and forces warmer air to exit
at high vents (at ridges). As wind (air) flows over a building, it creates positive
and negative pressures. Positive pressure forces air into the attic and negative
pressure draws air out of the attic. Convection or natural flow is used for
ventilation design. Nature or mechanical equipment can provide ventilation.
A natural system relies on convection for ventilation. A mechanical system is
designed to circulate a certain amount of air change per unit time. For both
system types, intake vents are placed along the eaves and exhaust vents are
placed along the ridge. A clear continuous path is needed between the intake
and exhaust vents. The required amount of attic ventilation is stated in the
building code and is a function of attic horizontal area. Most codes (Uniform
Building Code, BOCA) require one square foot of ventilation for every 150 square
feet of attic floor area. The reduction of vent area due to vent covers needs
to be included when calculating the required vent area. The Code ventilation
requirement does not directly address ice dams.
The Cold Regions Research Engineering Laboratory (CRREL) performed studies on
several buildings with varying degrees of ice dams at Fort Drum, New York. This
study consisted of placing instruments in the attics of buildings with histories
of minor to severe ice damming. The CRREL study found that to avoid ice dams,
the attic ventilation systems, natural or mechanical, should be sized to keep
the roof surface below freezing when the outside temperature is 22? F. When
the outside temperature is below 22? F, the outside air will circulate the attic
air easily. When above 22? F, it is unlikely that the melt water will refreeze
at the eave. Fifty-seven buildings at Fort Drum were modified according to these
guidelines and the previous chronic ice dams were eliminated.
Materials
Conventional roofing materials, such as shingles, wood shakes, and metal panels
are used for steep-sloped roofs in cold regions. Specifying the appropriate
underlayment at locations susceptible to ice dam formation is an important design
consideration. For example, an impermeable underlayment is needed at areas susceptible
to ice damming (e.g., overhangs). The underlayment should be installed over
the length of the overhang and extend past the exterior wall into the conditioned
space; about three feet is recommended at severe icing locations.
Heated Roof Products
Products that control or eliminate ice dams by heating the roof surface in areas
susceptible to ice dam formation range from an exposed wire on top of the roof
to heating elements incorporated into the roofing material. The simplest, an
exposed wire on top of the roof, creates tunnels in the snow and ice that direct
water toward the eave. This system does not stop ice dam formation; it creates
drainage outlets for the melt water. It is susceptible to weathering and can
be a fire hazard. This type of product has a short warranty (typically one year)
and a short service life ranging from three to five years. More extensive options
include roof products that integrate the heat element into the roofing. Products
are available for metal roofing, shingles, and shake and have five-year warranties.
The heating roof product can be attached to a timer or temperature/snow sensor
for activation in remote or partially habited locations. These heated shingles
are placed at locations susceptible to ice dams. While functioning, the heated
roof surface prevents ice and snow formation. Although these systems can be
less expensive and extensive in scope of work than improving the attic insulation
and ventilation characteristics, they rely on electrical power to function properly.
Preventive Maintenance
Preventive maintenance can reduce the chances of ice dam development. Inspecting
and removing leaves, sticks, and other debris from gutters and downspouts in
the fall will allow water to flow through the gutter and downspout systems as
intended. During the winter, keep the snow load to a minimum on the roof, especially
along eaves and overhangs. A roof rake (a long-handled tool) allows a ground-based
user to pull the snow off the roof. Care is required so that the roof is not
damaged during snow removal. In addition, gutters and downspouts should be kept
free of snow and ice formations, allowing a path for melted snow to exit the
roof.
Ice accumulation can be removed by artificial heat (e.g., steam, electric heaters). Direct ice removal with hammers, chisels, and shovels is not recommended due to the high probability of roof damage. The best method is to let it melt naturally.
Investigation Techniques
For buildings with ice dam problems, an evaluation should be performed to determine
the cause of the ice dams and the appropriate scope of repairs prior to the
start of work. Typical repairs usually consist of improving the attic ventilation
and/or ceiling insulation/vapor barrier. Buildings with complicated roof framing
or extensive mechanical systems in the attic make these types of repairs labor
intensive, difficult to perform, and expensive. A less expensive option is heated
roof surfaces at ice dam locations.
A typical investigation sequence includes the following elements:
• Review available drawings and other ice dam-related documents
• Observe site conditions (visual observations and destructive exploratory
testing)
• Surveying and testing, as required
• Develop repair recommendations
Observations
The following conditions should be observed: ice dam locations, existing intake
and exhaust roof venting, roof/ceiling construction, and penetrations in the
ceilings. Exploratory probing entails removing sections of finishes to expose
the underlying conditions. This provides information regarding the as-built
conditions but it is expensive and not performed on all projects.
Survey
An infrared thermographic (IR) survey identifies heat leak locations in the
ceiling assembly. As the temperature rises, infrared radiation gains in intensity.
An IR camera will graphically show areas and locations of heat leaks, aiding
in focusing the repair scope of work. IR surveys should be performed at night
when the temperature contrast is the greatest.
Testing
Air infiltration tests can determine large sources of air leakages; small air
leaks are difficult to locate during this test. Typically, a fan creates a lower
pressure in the room/living space to be tested. Wall openings are sealed with
tape so as not to influence the testing. The ceiling is then inspected for air
leaks that can be detected by touch or sound.
Summary
• Ice dams, ridges of ice that occur along eaves with overhangs, can
result in interior leakage and safety concerns.
• Keeping the roof surface cold with insulated ceilings and adequate attic
ventilation is the best method to prevent ice dams. In addition, specifying
the appropriate roofing materials in areas susceptible to ice damming to prevent
leakage at underlayment laps is also important.
• Ice dam remediation ranges from heating the roof surface to increasing
ceiling insulation and attic ventilation.
• Preventive maintenance, such as ensuring the roof drainage system functions
properly and minimizing snow accumulation on the roof, reduces the effects of
ice dams.
• Infrared thermographic surveys and air infiltration testing can assist
in locating sources of heat leakage and focusing the repairs on these locations.