Specifying Below-Grade Waterproofing
For more information, visit www.galeassociates.com.
Waterproofing is the treatment of a structure’s surface to prevent the passage of water under hydrostatic head or standing water conditions. It is used for foundation walls and sub-structures, slabs-on-grade, plaza decks, planters and green roofs, sumps and elevator pits, and between slabs or split slabs.
There are various options when designing waterproofing systems and specifying their components. However, selecting the correct products is dependent upon criteria and applications often beyond the design professional’s control. Therefore, a full understanding of the properties and limitations of these materials is critical when designing waterproofing systems. This article focuses on vertically- and horizontally-applied membrane systems and typical auxiliary flashings and accessories.
Types of waterproofing applications
The first step in selecting the most appropriate waterproofing system involves
determining when and where it is to be employed on the building. In standard
construction projects, positive-side waterproofing is generally applied directly
to the face of the structure exposed to water (or hydrostatic head of water).
Negative-side waterproofing, on the other hand, is applied interior to the exposed
structure, either in the wall or on the inside face of the wall—it has
no direct exposure to ground water. Finally, blind-side waterproofing is affixed
to an adjacent structure or soil retention feature (e.g. slurry wall), rather
than the new structural wall. It is ‘blind’ because one cannot see
the finished product sandwiched between the wall and the neighboring property.
Table 1 (page XX) provides examples of the various waterproofing systems.
Positive-side waterproofing
Positive-side waterproofing is installed during new construction on the exterior
of the new structure or after removing the overburden for an existing one. It
requires access to the outside face of the structure—when this is impossible,
blind- or negative-side techniques are often necessary. Positive-side waterproofing
can be seen as the least problematic and most successful method because, when
installed and designed correctly, the water pressure forces it to work. The
design team has the ability to inspect all the lap joints and defects in the
membrane with full visibility. However, the major disadvantage with positive-side
waterproofing is when there are leaks due to faulty installation or building
movement, repairs can only be made through excavation or negative-side waterproofing
techniques.
Negative-side waterproofing
Negative-side waterproofing is typically applied on existing construction in
remedial applications when exterior access is unfeasible. This approach only
protects inner surfaces. Generally, negative-side waterproofing is used more
for problem-solving than problem prevention. It is not as effective as positive-side
waterproofing because structures are subject to movement and cracking. When
this happens subsequent to the initial installation, additional applications
of negative-side products may be needed to close up the new gaps. However, ease
of application often makes this type of waterproofing the preferred choice when
exterior or positive-side techniques are not options.
Blind-side waterproofing
Blind-side waterproofing is used on new construction projects where property
line encroachment or other space limitations prohibit the ability to excavate
the site. It is also used for split- or mud-slab horizontal applications because
the products are waterproofing the underside of the structural slab. While the
various types of products mentioned in this article are available for blind-side
waterproofing, the technique’s installation typically involves using bentonite
layers in sheet forms, with or without a protective membrane.1 It is installed
dry, activating as it becomes wet from either the newly poured in-place concrete,
ground water, or water runoff. The bentonite layer of the sheet is applied against
the concrete structure, with the expansive action of the clay filling voids
or cracks in the structural concrete component. Confinement of the panels by
backfilling or treatment of the lagging is critical to ensure the expanding
clay is contained and gels or expands into the cracks, holes, and fissures of
the structure, rather than escaping into a void.
Design selection criteria
The following paragraphs outline the various design aspects one must consider
when it comes time to determine the best waterproofing system for a building.
Site conditions
Location can immediately dictate the need for blind-side techniques. When the
building site is maximized to the property line, there is simply no opportunity
to employ positive-side waterproofing since an installer will be unable to work
between the new and existing structures.
Hydrostatic pressure
The hydrostatic pressure on-site also determines the type of system most suitable.
Due to their relative tensile strength, bentonite products (blind-side or positive-side)
and elastomeric sheets chemically or heat-welded to a monolithic condition are
more likely to resist high hydrostatic pressures than peel-and-stick or fluid-applied
systems. 2
Temperature limitations
Temperature limitations should also be considered when selecting the membrane.
Many waterproofing products are difficult to install properly when the temperature
falls below 4 C (40 F). This is especially critical when solvents, adhesives,
and sealants are necessary for a particular system. Manufacturer product requirements
for cold- and hot-temperature storage and application limitations must be followed.
Drainage
Proper drainage is critical in both horizontal and vertical applications. Some
membrane types, such as hot-rubberized asphalt (HRA), can be used on very low
or no-slope plaza deck applications. However, HRA systems cannot be installed
on lightweight concrete fill. The drainage of vertical waterproofing can be
enhanced with larger cross-section drainage boards (e.g. base drain) and may
be piped into weep tubes discharging into below-slab drainage media. The drains
on plaza or terrace installations can be of the spot or trench variety, depending
on the ability to develop slope in the structure or with tapered insulation
(below the membrane). Single-ply membrane types, such as those made of polyvinyl
chloride (PVC) or thermoplastic polyolefin (TPO), are typically used on sloped
surfaces. In all cases, some type of drainage should be developed atop the membrane
to efficiently remove the water from the surface.
Insulation
When necessary, the building’s thermal performance can be enhanced by
adding insulation to the system. When this insulation is to be in direct contact
with water, such as below-grade on foundation walls or in a protected roofing
assembly, it should be a product able to withstand absorption (e.g. extruded
polystyrene [XPS]). Insulation beneath or above the waterproofing membrane can
be designed in a manner consistent with roofing design practices.
Structural integrity
Generally, the structural integrity of the building is unaffected by waterproofing
systems. However, green roofs, plazas with pavers, and other overburden materials
need to be analyzed for dead load, snow conditions, live load, and construction
loads in accordance with sound engineering principles. This article does not
address the very important aspects associated with the structural requirements
of roof, plaza, and foundation assemblies.
Building codes
Building codes in the region of the project (e.g. International Building Code
[IBC] 1806.3.2, Building Officials & Code Administrators [BOCA] National
Building Code 1813.4.2.2, Uniform Building Code [UBC] Chapter 18, and Southern
Building Code [SBC] Section 1814) require a waterproofing membrane in areas
where hydrostatic conditions exist. Each code defines the minimum required waterproofing
system and allows the designer to select from four to seven choices that bridge
non-structural cracks. Detailing and installation specifications are based on
the designer’s discretion and manufacturer’s requirements, as well
as code conformance.
Detailing
Proper detailing of penetrations, joints, and transitions is mandatory to satisfactorily
address water intrusion regardless of the type of system. The locations of tie-backs,
rakers, and walers in a blind-side system are likely the potential water entry
areas, where cracks in the concrete often occur. Coincidentally, these areas
are also the most difficult to install in the field due to requirements for
sealing, stripping, and cutting off steel sections. Therefore, the designer
should give special attention to the detailing and the owner or design team
should consider using the services of a field monitor to carefully evaluate
the application.
Penetrations, cracks, and construction joints
Although this point may seem fairly obvious, most leaks through foundation walls
occur at penetrations, cracks, or construction joints in the concrete. Since
the penetrations and joints are predetermined, waterstops and joint (i.e.link)
seals at these areas are straightforward to specify. Cracks are more difficult
to predict, so their treatment can be specified on positive-side applications
and dealt with in the field. On blind-side applications, the bentonite gel should
enter and close up the cracks. Grouting injections can also be made after fissure
propagation to seal the concrete (these repairs become more of a negative-side
application). Many positive-side products span minor cracks that develop in
the curing concrete substrate. To prevent oxidation and further cracking, care
should be exercised to protect the reinforcing steel in the concrete wall (i.e.
the grout should be forced into the fissure and then extend through the wall
past the steel).
Weighing the options
Each of the three application techniques are dependent on the design criteria
discussed. Suitability of certain systems will have a greater or lesser impact
depending on the limiting factors, such as hydrostatic pressure or application
temperature. After the application technique is determined, the designer must
weigh the important criteria to pare down the material choices to those most
appropriate for the given conditions. For example, suppose the designer is given
an accessible wall with hydrostatic head less than 15.2 m (50 ft) and cold weather
considerations. The designer could specify a positively applied system of a
fluid-applied membrane with minimum application temperature of about 7 C (20
F) – a good economic choice with acceptable performance expectations.
However, when an application is to be made at a tunnel with tensile forces greater
than 15 MPa (2175 psi), the designer would be advised to choose a high-strength
material such as 2.5-mm (100-mil) PVC.
Products overview
The waterproofing system components are fairly basic with few accessories. Although
the installation of the blind-side products begins at the outside of the structure,
this article outlines the materials from the inside-out to accommodate the proper
sequence of the positive-side application. Most product lines have applicability
in either a vertical or a horizontal installation.
Primers (typically spray-applied) may be required on the concrete depending upon membrane type—they are appropriate for bitumen-based systems, as well as other liquid membranes. The membrane itself can be, as outlined above, any of the modified bitumen (mod-bit) pre-formed sheets or hot-/cold-applied rubberized asphalt products. The pre-formed sheets are adhered at the seams and the rubberized asphalt products are liquid-applied and seamlessly monolithic. PVC and TPO single-ply sheets are heat-welded at the seams and flashing areas. Adhesively seamed systems, on the other hand, exhibit poor performance characteristics under moist conditions. It is this author’s opinion they are inappropriate for waterproofing applications. As stated in the Department of Defense (DoD) MIL-HDBK 1001/5A, Handbook on Roofing and Waterproofing, defective laps are vulnerable to rainwater ponding and freezing conditions that break down the performance of the adhesive.
Latex, asphaltic, and cementitious coatings are applied using a spray or a trowel. These systems, like the rubberized asphalt product, are monolithic in nature. Capillary products are crystalline materials mixed into the concrete or surface-applied. They are designed to penetrate the concrete to seal the capillaries. Metal oxide products are applied to the concrete surface as a slurry of cement, iron, and water—they swell upon rusting to form a protective coating over the concrete.
Bentonite waterproofing products are sheets of membrane with bentonite clay laminated to polyethylene sheets or woven into a geotextile core. The sheets are lapped and sealed or simply lapped. The expansion of the clay works as a protective cover for the concrete but also swells to fill small cracks and voids in the concrete. As described above, these products are used in blind-side applications, but can also be applied directly to cured concrete substrates using positive-side waterproofing techniques.
Drainage sheets are important to the system’s anticipated service life and the structure’s protection. The panels are typically three-dimensional, high-impact, dimpled plastic attached to a woven geotextile fabric. They channel water away from the membrane and relieve hydrostatic pressures against the waterproofing system.
Protection layers are sometimes incorporated into the waterproofing system
to protect against traffic and backfilling operations. Depending on the membrane,
the protection can be asphaltic boards, insulation, or even another layer of
high-density polyethylene (HDPE). An insulation layer can also be used for thermal
improvements to the structure. Generally, a plaza deck waterproofing system
includes an insulation layer, with XPS being the best choice when water is expected
to come into contact with the insulation.
Depending on the system, accessories can range from sealants to adhesives and fasteners to flashing sheets and mastics. Each product is required to completely form a waterproof bond to the structure and deal with integral flashing components at terminations, penetrations, and transitions. The designer should attempt to stay within the same family of products by a manufacturer (or its sister companies) to maintain single-source responsibility for any warranty issues. These concerns even include products such as pavers for plaza deck waterproofing projects.
Waterstops are necessary to provide a final level of protection for the building. These products are within the concrete section, especially at construction joints and sometimes at control joints. The most common pre-manufactured joint seals are:
• PVC or chloroprene rubber that need to be welded or otherwise fused
together;
• bentonite clay with/without butyl binders that expand when wet; and
• hydrophobic injectable expanding grouts.
The splices are critical to maintaining a watertight construction. There are also perforated hoses for injecting and re-injecting resins that allow for some joint movement (as do the rubber and PVC ‘bulbed’ waterstops). The waterstops should always be placed allowing for minimal cover in the concrete to prevent section blow-outs. They should be kept out of the keyway and outside the reinforcing steel to ensure dryness during installation while awaiting the concrete pour. This also provides a line of defense for the steel reinforcing in the wall. Trapping moisture in the wall beyond the steel may result in the unwanted deterioration of the alloy. It is critical to thoroughly coordinate all the trades (e.g. plumbers, electricians, concrete workers, waterproofers) to ensure correct placement of the appropriate waterstops and to reduce the potential for damage.
Conclusion
Waterproofing below-grade building elements is critical to keeping a facility
watertight. While there are many excellent systems in the marketplace that can
be specified and installed, the key point to success is understanding the benefits
and limitations for any particular system. Proper design and inspection is well
worth the effort, especially considering the cost of excavating and replacing
a failed system. The guarantees/warranties for any particular system vary based
on materials selected and details used. As they typically range from five to
20 years, the specifier should contact the material manufacturer for actual
requirements. Proper design inspection is imperative for all systems no matter
what guarantee or warranty is provided.
Notes
1 For more information on blind-side waterproofing and bentonite systems, see
“Specifying Bentonite Waterproofing” by Stacy Byrd, CDT (CS June
2004).
Additional Information
Author
Gary W. Brown, PE, has more than 20 years of experience in all aspects of building
technology, including the evaluation and design of repairs to roofs, walls,
waterproofing, windows, and the structure itself. He is an engineer working
out of the Fairfax, Virginia, office of consulting firm, Gale Associates Inc.
Brown can be contacted via e-mail at gwb@ gainc.com.
Abstract
Due to increased use of these below-grade structures for critical occupancies
(e.g. electrical equipment), waterproofing is becoming much more prevalent (and
necessary). This article addresses various systems, such as positive/negative
side waterproofing, plaza deck assemblies, and garden roof designs, while analyzing
pre-manufactured membranes, spray-on or brush-applied coatings, and expandable/injectable
waterstops.